Class BaseMValveFo
Version 1.1
Modified 28-SEP-2005 14:04:38.58
Code PlcTemplate
 Plc function object to BaseMValve.


 Connect the function object to an object of class or subclass of
 BaseMValve.

See also



RtBody attributes pwr_sClass_BaseMValveFo
Boolean ExtOrder ord Order input, that controls the order output when the valve
is in auto mode.
Boolean ExtInterlock ilk Valve interlock. The order is reset regardless of mode as long as
interlock is set.
Note that the interlocking does not affect the mode.
Boolean LocalMode loc The valve is in local control.
LocalUsed has to be configured in the CompModeDM object to be able
to set local mode.
Boolean LocalOrder lor Order when the valve is in local mode.
Boolean DisableSup dis Disable supervision. Alarm messages are suppressed.
AttrRef PlcConnect   The main object connected to this function object.

DevBody attributes 
pwrs:Class-$PlcNode PlcNode  


GraphPlcNode
object_type 11
parameters[0] 5
parameters[1] 1
parameters[2] 0
parameters[3] 0
subwindows 1
subwindow_class[0] pwrb:Class-WindowPlc
graphmethod 0 (standard, individual attributes)
graphindex 0
default_mask[0] 1
default_mask[1] 0
segname_annotation 1
compmethod 58
compindex 0
tracemethod 0
traceindex 0
connectmethod 10
executeordermethod 2
objname MValveFo
graphname MValveFo


Template Object


Attributes detail


ExtOrder Input
Class Input
Type Boolean
Flags Noinvert
GraphName ord
Body RtBody
 Order input, that controls the order output when the valve
 is in auto mode.

ExtInterlock Input
Class Input
Type Boolean
Flags Noinvert
GraphName ilk
Body RtBody
 Valve interlock. The order is reset regardless of mode as long as
 interlock is set.
 Note that the interlocking does not affect the mode.

LocalMode Input
Class Input
Type Boolean
Flags
GraphName loc
Body RtBody
 The valve is in local control.
 LocalUsed has to be configured in the CompModeDM object to be able
 to set local mode.

LocalOrder Input
Class Input
Type Boolean
Flags
GraphName lor
Body RtBody
 Order when the valve is in local mode.

DisableSup Input
Class Input
Type Boolean
Flags Noinvert
GraphName dis
Body RtBody
 Disable supervision. Alarm messages are suppressed.

PlcConnect Intern
Class Intern
Type AttrRef
Flags
Body RtBody
 The main object connected to this object.
 This attribute is set when the function object is connected from
 the plc editor by the connect function.

PlcNode Buffer
Class Buffer
Type pwrs:Class-$PlcNode
Flags
Body DevBody