| Volume pwrb | |
| Attributes: Runtime | Development | System | Template | Detail C Binding: Struct | Class | Code  ClassTree | INDEX NO INDEX |
Class CStoSv
|
||
|---|---|---|
| Version | 1.0 | |
| Modified | 08-MAR-2026 11:05:32.00 | |
| Code | rt_plc_macro_string.h | |
Conditional storage of string value.

Conditional storage of a string value on a specified local Sv object. Conditional is aimed at the con-input, which is supposed to be connected. The conditional input signal can be inverted by means of the Attribute Editor. The string input can be connected to an output of type String. It can also be hidden and instead, a constant string can be inserted, as a value of the input. The constant string is displayed in the plc-sheet. It is not allowed, by means of a function in C or PLC programs, to write in any of the inputs.
| RtBody attributes pwr_sClass_cstosv | |||
|---|---|---|---|
| String80 | In | VAL | Input string. |
| Boolean | Cond | con | Specifies whether a storage will be done or not. FALSE means no storage and TRUE means storage of an analog value. |
| DevBody attributes | |||
|---|---|---|---|
| AttrRef | SvObject | In | Specifies the name of the object where to store the value. |
| Int32 | SvObjectSegments | Specifies how many segments of the Sv object name that is to be displayed in the symbol of the CStoSv object. The segments are counted from behind. |
|
| PlcNode | PlcNode | ||
| GraphPlcNode | |
|---|---|
| object_type | 261 |
| parameters[0] | 2 |
| parameters[1] | 0 |
| parameters[2] | 0 |
| parameters[3] | 0 |
| subwindows | 0 |
| graphmethod | 8 |
| graphindex | 1 |
| default_mask[0] | 3 |
| default_mask[1] | 0 |
| segname_annotation | 0 |
| devbody_annotation | 1 |
| rtbody_annotation | 1 |
| compmethod | 11 |
| compindex | 0 |
| tracemethod | 0 |
| traceindex | 1 |
| connectmethod | 18 |
| executeordermethod | 2 |
| objname | CStoSv |
| graphname | CStoSv |
| debugpar | Cond |
| Template Object | |
|---|---|
| Cond | 1 |
| In Input | ||
|---|---|---|
| Class | Input | |
| Type | String80 | |
| Flags | RTVIRTUAL | DEVBODYREF | |
| GraphName | VAL | |
| Body | RtBody | |
The input is connected to a string value or left open. In the latter case the value of In, is considered to be stored.
| Cond Input | ||
|---|---|---|
| Class | Input | |
| Type | Boolean | |
| Flags | STATE | RTVIRTUAL | DEVBODYREF | NOEDIT | |
| GraphName | con | |
| Body | RtBody | |
Specifies whether a storage will be done or not. FALSE means no storage and TRUE means storage of an analog value.
| SvObject Intern | ||
|---|---|---|
| Class | Intern | |
| Type | AttrRef | |
| Flags | ||
| GraphName | In | |
| Body | DevBody | |
Specifies the name of the object where to store the value.
| SvObjectSegments Intern | ||
|---|---|---|
| Class | Intern | |
| Type | Int32 | |
| Flags | ||
| Body | DevBody | |
Specifies how many segments of the Sv object name that is to be displayed in the symbol of the CStoSv object. The segments are counted from behind.
| PlcNode Buffer | ||
|---|---|---|
| Class | Buffer | |
| Type | PlcNode | |
| Flags | INVISIBLE | |