| Volume pwrb | |
| Attributes: Runtime | Development | System | Template | Detail C Binding: Struct | Class | Code  ClassTree | INDEX NO INDEX |
Class CStoNumSp
|
||
|---|---|---|
| Version | 1.0 | |
| Modified | 08-MAR-2026 11:05:32.00 | |
| Code | rt_plc_macro_string.h | |
Conditional Storage of number of characters in a string attribute.

Conditional storage of an string value ( parameter, input, or output signal) on a specified attribute in a local object. Conditional is aimed at the con-input, which is supposed to be connected. The last name segment of the object and the name of the parameter will be shown in the right part of the CStoNumSp symbol. It is not allowed, by means of a function in C or PLC programs, to write in any of the inputs.Example
It is possible to use CStoNumSp to change the DetectText in ASup or DSup objects.
| RtBody attributes pwr_sClass_cstonumsp | |||
|---|---|---|---|
| String80 | In | VAL | The input is connected to an analog signal or left open. In the latter case the In is considered to be stored. |
| Boolean | Cond | con | Specifies whether a storage will be done or not. FALSE means no storage and TRUE means storage of an analog value. |
| DevBody attributes | |||
|---|---|---|---|
| AttrRef | Object | sts | Specifies the name of the object where to store the value. |
| Int32 | ObjectSegments | Specifies how many segments of the actual object name that is to be displayed in the symbol of the CStoNumSp object. The segments are counted from behind. 0 and 1 both result in displaying the last segment of the actual object name. |
|
| Int32 | NumberOfChar | Specifies number of character to copy. If the string is shorter than NumberOfChar the string and the NULL termination is copied. If the lengh of the string is equal or greater than NumberOfChar, the NULL termination is not copied. In this case the previous string in the target attribut should be larger than NumberOfChar. If not, the NULL termination is lost and the result is undefined. |
|
| PlcNode | PlcNode | ||
| GraphPlcNode | |
|---|---|
| object_type | 272 |
| parameters[0] | 2 |
| parameters[1] | 0 |
| parameters[2] | 0 |
| parameters[3] | 0 |
| subwindows | 0 |
| graphmethod | 15 |
| graphindex | 0 |
| default_mask[0] | 3 |
| default_mask[1] | 0 |
| segname_annotation | 0 |
| devbody_annotation | 1 |
| compmethod | 12 |
| compindex | 0 |
| tracemethod | 0 |
| traceindex | 1 |
| connectmethod | 7 |
| executeordermethod | 2 |
| objname | CStoNumSp |
| graphname | CStoNumSp |
| debugpar | Cond |
| Template Object | |
|---|---|
| Cond | 1 |
| In Input | ||
|---|---|---|
| Class | Input | |
| Type | String80 | |
| Flags | RTVIRTUAL | DEVBODYREF | |
| GraphName | VAL | |
| Body | RtBody | |
The input is connected to an analog signal or left open. In the latter case the In is considered to be stored.
| Cond Input | ||
|---|---|---|
| Class | Input | |
| Type | Boolean | |
| Flags | STATE | RTVIRTUAL | DEVBODYREF | NOEDIT | |
| GraphName | con | |
| Body | RtBody | |
Specifies whether a storage will be done or not. FALSE means no storage and TRUE means storage of an analog value.
| Object Intern | ||
|---|---|---|
| Class | Intern | |
| Type | AttrRef | |
| Flags | ||
| GraphName | sts | |
| Body | DevBody | |
Specifies the name of the object where to store the value.
| ObjectSegments Intern | ||
|---|---|---|
| Class | Intern | |
| Type | Int32 | |
| Flags | ||
| Body | DevBody | |
Specifies how many segments of the actual object name that is to be displayed in the symbol of the CStoNumSp object. The segments are counted from behind. 0 and 1 both result in displaying the last segment of the actual object name.
| NumberOfChar Intern | ||
|---|---|---|
| Class | Intern | |
| Type | Int32 | |
| Flags | ||
| Body | DevBody | |
Specifies number of character to copy. If the string is shorter than NumberOfChar the string and the NULL termination is copied. If the lengh of the string is equal or greater than NumberOfChar, the NULL termination is not copied. In this case the previous string in the target attribut should be larger than NumberOfChar. If not, the NULL termination is lost and the result is undefined.
| PlcNode Buffer | ||
|---|---|---|
| Class | Buffer | |
| Type | PlcNode | |
| Flags | INVISIBLE | |
| Body | DevBody | |