Class PiPos
Version 1.0
Modified 08-MAR-2026 11:05:32.00
Code rt_plc_io.c
 Translates a pulse counter value into an engineering
 value, e.g. position, volume etc.

 Suppose the engineering value is a position. The actual
 position is then calculated at every scanning by means
 of the straight line equation
         ActVal = Gain * (PulsIn - PiCal1) + PosCal1

 The ActVal position is calculated relative to the
 position in calibration point 1 by means of the current
 pulse signal, PulsIn, saved pulse signal PiCal1, and
 saved position, PosCal1, at calibration point 1. The
 Gain factor is either specified or calculated by means
 of a second calibration point, calibration point 2.
 How to carry out the calibrations is described below
 under Calibration.


RtBody attributes pwr_sClass_pipos
Int32 PulsIn PI Pulse counter value, e.g. the pulse number PI or PIX
from a GetPi or Count object.
Float32 CalPos1 CP1 Specifies a position that will be used at the next
absolute value calibration at point 1.

The attribute can be assigned a value in the
development environment by means of the Attribute
Editor and in the target environment e.g. by means of a
function in C or PLC programs. If the input is
connected the value of the connected quantity is used
at calibration.
Boolean CalOrder1 co1 Calibration order 1.
Specifies whether to start an absolute value
calibration in point 1 or not. FALSE means no action.
The transition FALSE -> TRUE triggers the calibration
in point 1 and the pulse value PulsIn is read and
stored in PICal1, and the value of CalPos1 is moved
into PosCal1. A connected input signal is supposed to
be a pulse.

If the input left open it can be set from anywhere when
to trigger the calibration. In this case it is cleared
by the ProviewR system when it has been noticed.
Float32 CalPos2 CP2 Specifies a position that will be used at the next gain
factor calibration at point 2.

The attribute can be assigned a value in the
development environment by means of the Attribute
Editor and in the target environment, for instance, by
means of a function in C or PLC programs. If the input
is connected the value of the connected quantity is
used at calibration.
Boolean CalOrder2 co2 Calibration order 2.

Specifies whether to start a gain factor calibration in
point 2 or not. FALSE means no action. The transition
FALSE -> TRUE triggers the gain calibration in point 2.
A connected input signal is supposed to be a pulse.
If the input is left open it can be set from anywhere
when to trigger the calibration. In this case it is
cleared by the ProviewR system when it has been
noticed.
Float32 ActVal POS Current position. The unit comes from the unit of Gain.
If Gain is in mm per pulse then ActVal will be in mm.
Float32 Gain Gain If the conversion factor is denoted Omsfak is Omsfak =
the number of pulses per x-unit, where x-unit can be
mm, degrees etc. The Gain is obtained as the value of 1 / Omsfak.
The value is either specified or calculated; see
Calibration below.
Int32 PICal1 PICal1 Pulse counter value at the last absolute value
calibration at point 1. Its corresponding position
value is specified by PosCal1.
Boolean CalOrder1Old CalOrder1Old Used at edge detecting.
Boolean CalOrder2Old CalOrder2Old Used at edge detecting.
Float32 PosCal1 PosCal1 Position value at the last absolute value calibration
at point 1. Its corresponding pulse counter value is
specified by PiCal1. PosCal1 has the same unit as
ActVal.
Float32 PosCal2 CalPos2 Position value at the last gain calibration at point 2.
Int32 AccCalPos1 AccCalPos1 The operator's authorities regarding CalPos1
respectively CalOrder1.

0 -- Changes not allowed.
!= 0 -- Changes allowed.
Int32 AccCalOrder1 AccCalOrder1 The operator's authorities regarding CalPos2
respectively CalOrder2.
0 -- Changes not allowed.
!= 0 -- Changes allowed.
Int32 AccCalPos2 AccCalPos2 The minimum and maximum allowed value of CalPos1 at
changes made by an operator.
Int32 AccCalOrder2 AccCalOrder2
Float32 MinCalPos1 MinCalPos1 The minimum and maximum allowed value of CalPos2 at
changes made by an operator.

Calibration
Determination of absolute position. Calibration by
means of calibration point 1.

In fact, there are four different methods to determine
the absolute position:
1 No calibration. At configuration specifies the pulse
value PICal1 when ActVal is equal to the known
position PosCal1. This method can be used if the
pulse value is known at a fixed position at the
configuration stage.

2 The operator calibrates. The operator specifies the
position CalPos1 and then gives order to calibrate
by setting CalOrder1.
3 Automatic calibration at a fixed position. Connects
co1 to a digital signal. Specify the corresponding
position in CalPos1. At a leading edge on CalOrder1
the pulse value PulsIn is read and stored in PICal1,
and the value of CalPos1 is moved into PosCal1.

4 Automatic calibration against a varying position.
The same as for a fixed position but CalPos1 is also
connected to a calculated position signal. At a
leading edge on CalOrder1 the pulse value PulsIn is
read and stored in PICal1, and PosCal1 is updated by
a value from the external signal.
Automatic calibration ought to be done at low speed
to avoid position error.

Determination of gain. Calibration by means of
calibration point 2.
1 No calibration.
The designer specifies the value of Gain; (= the
difference in position per pulse). This is the
normal case when the characteristic of the position
transducer is known. If the conversion factor is
denoted Omsfak , Omsfak is equal to the number of
pulses per x-unit, where x-unit can be mm, degrees,
etc. The Gain is obtained as the value of 1 /
Omsfak.
2 Moment 2, 3 and 4 as for absolute position above.
The calibration in point 1 has to be done first.
Then a calibration is carried out in point 2, at
which a new position and its corresponding pulse
value are read. The values are compared with those
from point value, and Gain is calculated.

Automatic calibration of the gain is supposed to be
unusual. However it is possible that there is a need
of re-calibration at exchange of measuring unit.
Float32 MaxCalPos1 MaxCalPos1
Float32 MinCalPos2 MinCalPos2
Float32 MaxCalPos2 MaxCalPos2

DevBody attributes 
PlcNode PlcNode  


GraphPlcNode
object_type 69
parameters[0] 5
parameters[1] 0
parameters[2] 1
parameters[3] 0
subwindows 0
graphmethod 0 (standard, individual attributes)
graphindex 0
default_mask[0] 1
default_mask[1] 1
segname_annotation 1
compmethod 4
compindex 0
executeordermethod 2
objname PiPos
graphname PiPos
debugpar


Template Object
Gain 1.0
AccCalPos1 15
AccCalOrder1 15


Attributes detail


PulsIn Input
Class Input
Type Int32
Flags STATE | NOEDIT | REDUTRANSFER
GraphName PI
Body RtBody
 Pulse counter value, e.g. the pulse number PI or PIX
 from a GetPi or Count object.

CalPos1 Input
Class Input
Type Float32
Flags REDUTRANSFER
GraphName CP1
Body RtBody
 Specifies a position that will be used at the next
 absolute value calibration at point 1.

 The attribute can be assigned a value in the
 development environment by means of the Attribute
 Editor and in the target environment e.g. by means of a
 function in C or PLC programs. If the input is
 connected the value of the connected quantity is used
 at calibration.

CalOrder1 Input
Class Input
Type Boolean
Flags STATE | NOEDIT | NOINVERT | REDUTRANSFER
GraphName co1
Body RtBody
 Calibration order 1.
 Specifies whether to start an absolute value
 calibration in point 1 or not. FALSE means no action.
 The transition FALSE -> TRUE triggers the calibration
 in point 1 and the pulse value PulsIn is read and
 stored in PICal1, and the value of CalPos1 is moved
 into PosCal1. A connected input signal is supposed to
 be a pulse.

 If the input left open it can be set from anywhere when
 to trigger the calibration. In this case it is cleared
 by the ProviewR system when it has been noticed.

CalPos2 Input
Class Input
Type Float32
Flags REDUTRANSFER
GraphName CP2
Body RtBody
 Specifies a position that will be used at the next gain
 factor calibration at point 2.

 The attribute can be assigned a value in the
 development environment by means of the Attribute
 Editor and in the target environment, for instance, by
 means of a function in C or PLC programs. If the input
 is connected the value of the connected quantity is
 used at calibration.

CalOrder2 Input
Class Input
Type Boolean
Flags STATE | NOEDIT | NOINVERT | REDUTRANSFER
GraphName co2
Body RtBody
 Calibration order 2.

 Specifies whether to start a gain factor calibration in
 point 2 or not. FALSE means no action. The transition
 FALSE -> TRUE triggers the gain calibration in point 2.
 A connected input signal is supposed to be a pulse.
 If the input is left open it can be set from anywhere
 when to trigger the calibration. In this case it is
 cleared by the ProviewR system when it has been
 noticed.

ActVal Output
Class Output
Type Float32
Flags STATE | NOEDIT | REDUTRANSFER
GraphName POS
Body RtBody
 Current position. The unit comes from the unit of Gain.
 If Gain is in mm per pulse then ActVal will be in mm.

Gain Intern
Class Intern
Type Float32
Flags REDUTRANSFER
GraphName Gain
Body RtBody
 If the conversion factor is denoted Omsfak is Omsfak =
 the number of pulses per x-unit, where x-unit can be
 mm, degrees etc. The Gain is obtained as the value of 1 / Omsfak.
 The value is either specified or calculated; see
 Calibration below.

PICal1 Intern
Class Intern
Type Int32
Flags REDUTRANSFER
GraphName PICal1
Body RtBody
 Pulse counter value at the last absolute value
 calibration at point 1. Its corresponding position
 value is specified by PosCal1.

CalOrder1Old Intern
Class Intern
Type Boolean
Flags STATE | NOEDIT | INVISIBLE | REDUTRANSFER
GraphName CalOrder1Old
Body RtBody
 Used at edge detecting.

CalOrder2Old Intern
Class Intern
Type Boolean
Flags STATE | NOEDIT | INVISIBLE | REDUTRANSFER
GraphName CalOrder2Old
Body RtBody
 Used at edge detecting.

PosCal1 Intern
Class Intern
Type Float32
Flags STATE | NOEDIT | INVISIBLE | REDUTRANSFER
GraphName PosCal1
Body RtBody
 Position value at the last absolute value calibration
 at point 1. Its corresponding pulse counter value is
 specified by PiCal1. PosCal1 has the same unit as
 ActVal.

PosCal2 Intern
Class Intern
Type Float32
Flags STATE | NOEDIT | INVISIBLE | REDUTRANSFER
GraphName CalPos2
Body RtBody
 Position value at the last gain calibration at point 2.

AccCalPos1 Intern
Class Intern
Type Int32
Flags
GraphName AccCalPos1
Body RtBody
 The operator's authorities regarding CalPos1
 respectively CalOrder1.

  0   -- Changes not allowed.
  != 0 -- Changes allowed.

AccCalOrder1 Intern
Class Intern
Type Int32
Flags
GraphName AccCalOrder1
Body RtBody
 The operator's authorities regarding CalPos2
 respectively CalOrder2.
  0   -- Changes not allowed.
  != 0 -- Changes allowed.

AccCalPos2 Intern
Class Intern
Type Int32
Flags
GraphName AccCalPos2
Body RtBody
 The minimum and maximum allowed value of CalPos1 at
 changes made by an operator.

AccCalOrder2 Intern
Class Intern
Type Int32
Flags
GraphName AccCalOrder2
Body RtBody

MinCalPos1 Intern
Class Intern
Type Float32
Flags REDUTRANSFER
GraphName MinCalPos1
Body RtBody
 The minimum and maximum allowed value of CalPos2 at
 changes made by an operator.

     Calibration
 Determination of absolute position. Calibration by
 means of calibration point 1.

 In fact, there are four different methods to determine
 the absolute position:
 1 No calibration. At configuration specifies the pulse
 value PICal1 when ActVal is equal to the known
 position PosCal1. This method can be used if the
 pulse value is known at a fixed position at the
 configuration stage.

 2 The operator calibrates. The operator specifies the
 position CalPos1 and then gives order to calibrate
 by setting CalOrder1.
 3 Automatic calibration at a fixed position. Connects
 co1 to a digital signal. Specify the corresponding
 position in CalPos1. At a leading edge on CalOrder1
 the pulse value PulsIn is read and stored in PICal1,
 and the value of CalPos1 is moved into PosCal1.

 4 Automatic calibration against a varying position.
 The same as for a fixed position but CalPos1 is also
 connected to a calculated position signal. At a
 leading edge on CalOrder1 the pulse value PulsIn is
 read and stored in PICal1, and PosCal1 is updated by
 a value from the external signal.
 Automatic calibration ought to be done at low speed
 to avoid position error.

 Determination of gain. Calibration by means of
 calibration point 2.
 1  No calibration.
    The designer specifies the value of Gain; (= the
    difference in position per pulse). This is the
    normal case when the characteristic of the position
    transducer is known. If the conversion factor is
    denoted Omsfak , Omsfak is equal to the number of
    pulses per x-unit, where x-unit can be mm, degrees,
    etc. The Gain is obtained as the value of 1 /
    Omsfak.
 2  Moment 2, 3 and 4 as for absolute position above.
    The calibration in point 1 has to be done first.
    Then a calibration is carried out in point 2, at
    which a new position and its corresponding pulse
    value are read. The values are compared with those
    from point value, and Gain is calculated.

    Automatic calibration of the gain is supposed to be
    unusual. However it is possible that there is a need
    of re-calibration at exchange of measuring unit.

MaxCalPos1 Intern
Class Intern
Type Float32
Flags REDUTRANSFER
GraphName MaxCalPos1
Body RtBody

MinCalPos2 Intern
Class Intern
Type Float32
Flags REDUTRANSFER
GraphName MinCalPos2
Body RtBody

MaxCalPos2 Intern
Class Intern
Type Float32
Flags REDUTRANSFER
GraphName MaxCalPos2
Body RtBody

PlcNode Buffer
Class Buffer
Type PlcNode
Flags INVISIBLE
Body DevBody