| Volume pwrb | |
| Attributes: Runtime | Development | System | Template | Detail C Binding: Struct | Class | Code  ClassTree | INDEX NO INDEX |
Class StoAp
|
||
|---|---|---|
| Version | 1.0 | |
| Modified | 08-MAR-2026 11:05:32.00 | |
| Code | rt_plc_macro_io.h | |
Store Analog parameter. Used in run time to write in analog parameters.

Stores an analog value in specified floating-point attribute ( scalar or element in 1-dimensional array by the type pwr_tFloat32) in a local object. The receiving attribute may not concern a pointer. The last name segment of the object and the name of the parameter will be shown in the right empty part of the StoAp symbol.
| RtBody attributes pwr_sClass_stoap | |||
|---|---|---|---|
| Float32 | In | VAL | The input is connected to an analog signal or left open. In the latter case In is default 0.0 and not adjustable in the run time system. The In attribute specifies which value should be assigned to the parameter. |
| DevBody attributes | |||
|---|---|---|---|
| AttrRef | Object | sts | Used by the PLC Editor. Specifies the complete name of the current attribute. |
| Int32 | ObjectSegments | Specifies how many segments of the actual object name that is to be displayed in the symbol of the StoAp object. The segments are counted from behind. 0 and 1 both result in displaying the last segment of the actual object name. |
|
| PlcNode | PlcNode | ||
| GraphPlcNode | |
|---|---|
| object_type | 256 |
| parameters[0] | 1 |
| parameters[1] | 0 |
| parameters[2] | 0 |
| parameters[3] | 0 |
| subwindows | 0 |
| graphmethod | 7 (Get,Set) |
| graphindex | 0 |
| default_mask[0] | 1 |
| default_mask[1] | 0 |
| segname_annotation | 0 |
| devbody_annotation | 1 |
| compmethod | 12 |
| compindex | 0 |
| tracemethod | 0 |
| traceindex | 0 |
| connectmethod | 7 |
| executeordermethod | 2 |
| objname | StoAp |
| graphname | StoAp |
| debugpar | |
| Template Object | |
|---|---|
| ObjectSegments | 2 |
| In Input | ||
|---|---|---|
| Class | Input | |
| Type | Float32 | |
| Flags | RTVIRTUAL | DEVBODYREF | |
| GraphName | VAL | |
| Body | RtBody | |
The input is connected to an analog signal or left open. In the latter case In is default 0.0 and not adjustable in the run time system. The In attribute specifies which value should be assigned to the parameter.
| Object Intern | ||
|---|---|---|
| Class | Intern | |
| Type | AttrRef | |
| Flags | ||
| GraphName | sts | |
| Body | DevBody | |
Used by the PLC Editor. Specifies the complete name of the current attribute.
| ObjectSegments Intern | ||
|---|---|---|
| Class | Intern | |
| Type | Int32 | |
| Flags | ||
| Body | DevBody | |
Specifies how many segments of the actual object name that is to be displayed in the symbol of the StoAp object. The segments are counted from behind. 0 and 1 both result in displaying the last segment of the actual object name.
| PlcNode Buffer | ||
|---|---|---|
| Class | Buffer | |
| Type | PlcNode | |
| Flags | INVISIBLE | |
| Body | DevBody | |